Sıfır bileşen akım trafosunun montajı için önlemler

Apr 05, 2023|

1. Kurulumdaki sorunlar
(1) Zero-sequence current transformer'>The current transformer should be installed on the bottom plate of the switch cabinet, and should be fixed by a reliable bracket. However, some manufacturers or construction units install the zero-sequence current transformer'>current transformer on the bracket under the bottom plate of the switch cabinet, and even bind the zero-sequence current transformer'>Tamamen kapalı şalt sistemi ilkesini ihlal eden kablo üzerindeki akım trafosu, bırakın küçük hayvanları, ne güvenli ne de toz geçirmezdir, birçok gizli tehlike bırakır.

(2) After the cable terminal passes through the external zero-sequence current transformer'>current transformer, the relative position of the cable's metal shielded grounding wire and the external zero-sequence current transformer'>current transformer is incorrect. According to the "Beijing Electrical Engineering Installation Regulations", the metal sheath at the terminal of the three-core power cable must be well grounded; the copper shield of each phase of the plastic cable and the steel armor should be tin-welded with the ground wire (oil-impregnated paper insulated cable lead-clad and armored) The ground wire should be welded), when the cable passes through the zero-sequence current transformer'>akım trafosu, kablo metal kılıfı ve topraklama kablosu topraktan yalıtılmalı ve kablo topraklama noktası (kablo topraklama kablosu ile kablo metal blendajı arasındaki kaynak noktası) transformatörün altındadır, topraklama kablosu doğrudan topraklanmalıdır ;

When the grounding point is above the transformer, the grounding wire should pass through the transformer for grounding. The grounding wire must be connected to the special grounding copper bar in the switch cabinet. The grounding wire must be copper stranded wire or tinned copper braided wire. The cross section of the grounding wire must be Meet the requirements of the regulations. During the inspection, it was found that some cable grounding wires should pass through the zero-sequence current transformer'>current transformer, and some cable grounding wires should not pass through the zero-sequence current transformer'>akım trafosu. Doğru davran.

(3) Due to the relatively large cable terminal, the magnetic circuit of the current transformer'>current transformer is not closed. At present, the commonly used 10kV power cables are three-core XLPE cables. >The current transformer cannot be put on, and the zero-sequence current transformer is disassembled during the construction'>The current transformer interface, the cable is put on, but the interface is forgotten to be restored; some are restored, but the interface is not restored strictly; some terminals The separation of the first three cores is thicker than the zero-sequence current transformer'>current transformer's inner diameter and just stuck in the middle of the zero-sequence current transformer'>current transformer so that the zero-sequence current transformer'>current transformer interface cannot be restored to close, resulting in Zero-sequence current transformer'>Akım trafosunun manyetik devresi kapalı değil ve normal çalışamıyor.

(4) The zero-sequence current transformer'>current transformer's secondary connection was opened during the cable construction, and it was not restored in time after the work was completed, causing the current transformer'>akım trafosunun sekonder bobini açılır.

(5) Kablo metal kılıflı topraklama telinin topraklama ucu terminale kaynaklanmamıştır veya şalt kabinindeki topraklama bakır çubuğuna bağlı değildir, ancak şalter kabini gövdesinin cıvatalarına gelişigüzel bir şekilde bindirilmiştir.

2. Doğru kurulum yöntemi
(1) Sıfır bileşen akım trafosu seçildiğinden emin olunmalıdır > akım trafosunun iç çapı, kablo terminal başlığının dış çapından daha büyüktür;

(2) Try not to dismantle the zero-sequence current transformer'>inşaat sırasında akım trafosu. Sökülmesi gerekiyorsa, iş bittikten sonra eski haline getirilmeli;

(3) The grounding wire must be copper stranded wire or tinned copper braided wire, the cross-section of the grounding wire should not be less than 25mm2, the grounding end should be welded with a terminal, and the grounding wire and the zero-sequence current transformer'>akım trafosu uygun şekilde kullanılmalıdır Topraklama telinin ilgili konumu, topraklama bakır çubuğuna kurulmalıdır;

(4) Sıfır bileşen koruma sistemi, korumanın normal şekilde çalışmasını sağlamak için güç açılmadan önce ayarlanmalıdır.